SGB series Un-packed H Grade Dry-type Transformer adopt (Germany) MORA dry type transformer specialtechnology, make products fully meet the fire waterproof and meet the requirements of environment protection. it isthe ideal product distribution system, widely used in the subway, ships, mining, chemical, electric power enterpriseand staff of dense buildings, etc. Various kinds of fire safety have special requirements occasion.
| Rated Capacity (KVA) |
Voltage combination | Connection group symbol |
No-load loss W |
Under the different insulayion heat-resisting rank load loss (W) |
No-oad current % |
Short-circuit impedance% |
||||
| (H.V.) kV |
High pressure tapping |
(L.V.) KV |
130℃(B) (100℃) |
155℃(F) (120℃) |
180℃(H) (145℃) |
|||||
| 30 | 6~11 | ±2×2.5 | 0.4 | Yyn0 Dyn11 |
105 | 605 | 640 | 685 | 2.4 | 4.0 |
| 50 | 155 | 845 | 900 | 965 | 2.4 | |||||
| 80 | 210 | 1160 | 1240 | 1330 | 1.8 | |||||
| 100 | 230 | 1330 | 1415 | 1520 | 1.8 | |||||
| 125 | 270 | 1565 | 1665 | 1780 | 1.6 | |||||
| 160 | 310 | 1800 | 1915 | 2050 | 1.6 | |||||
| 200 | 360 | 2135 | 2275 | 2440 | 1.4 | |||||
| 250 | 415 | 2330 | 1485 | 2665 | 1.4 | |||||
| 315 | 510 | 2945 | 3125 | 3355 | 1.2 | |||||
| 400 | 570 | 3375 | 3590 | 3850 | 1.2 | |||||
| 500 | 670 | 4130 | 4390 | 4705 | 1.0 | |||||
| 630 | 775 | 4975 | 5290 | 5660 | 1.0 | |||||
| 630 | 750 | 5050 | 5365 | 5760 | 1.0 | 6.0 | ||||
| 800 | 875 | 5895 | 6265 | 6715 | 1.0 | |||||
| 1000 | 1020 | 6885 | 7315 | 7885 | 1.0 | |||||
| 1250 | 1205 | 8790 | 8720 | 9335 | 10 | |||||
| 1600 | 1415 | 9945 | 10555 | 11320 | 1.0 | |||||
| 2000 | 1760 | 12240 | 13005 | 14005 | 0.8 | |||||
| 2500 | 2080 | 14535 | 15445 | 16605 | 0.8 | |||||
Heat condition is good. Hot long life, strong ability of self-learning, over load in over load, lP45 120% long-termconditions witnout forced air cooling, can long-term full load operation.
High security and flame retardant performance high temperature, at 800℃ when combustion without smoke long production.
Strong resistance to strike capability in 50℃ (can immediately add full load).
Unique coil struc tur e and strong field calculation, make products produced almost no partial discharge.